Water Ledger Michigan

Methods and sources

Model version and data date load below.

This is Michigan's full methods page. The model is the same in every state; how other states are built, and a methods page for each, are at methods for every state. How a data center's cooling system moves heat outdoors, the four cooling designs, the three cooling plant setups and their combinations, with figures: how a data center is cooled.

Estimates

For a data center of a given size, cooling design and Michigan climate region, Water Ledger estimates three amounts of water on an average day, on the hottest days (a 1-in-10-year peak day) and over a year:

Water used at power plants to make the electricity is shown separately and never added to these on-site numbers.

It also shows the place before and after: public water, the sewer plant, runoff, sediment, phosphorus, road salt, generator fuel and electricity, today and with the campus.

Methods overview

  1. Weather. Hourly temperature and dew point for 1995–2024 from the ERA5 reanalysis, for the 0.25° grid cell holding each place, about 28 by 20 km in Michigan (a reanalysis, not measured weather) . A place whose cell is less than half land takes the nearest cell that is at least half land. Each cell is corrected by quantile mapping toward hourly records at up to four stations within 100 km (NOAA ISD and Environment and Climate Change Canada). Cells less than 90% land, along the Great Lakes, run cool next to shore stations, so they are corrected only toward shore stations; cells at least 90% land, only toward inland stations. A place's page names the stations. Wet-bulb temperature from Stull's formula .
  2. Heat. The campus's electricity becomes heat that must be removed: computers, power losses, lighting, fans, pumps and chillers. Outside air, brought in to ventilate the building, adds or takes away a little more. Heat through the water or coil is all of that except the heat rejection fans, whose heat goes straight to the exhaust air (model 1.5). An economizer carries as much as the weather allows and chillers carry the rest .
  3. Evaporation. Evaporative cooling removes heat by evaporating water (about 1,050 BTU per pound). The share of heat removed by evaporation rises with air temperature; we use the relation from Rutberg et al. (2011) as given in the U.S. Geological Survey's method for cooling towers .
  4. Blowdown and drift. A small amount escapes as droplets (drift), a share of the water passing through the wet part of the cooler . Towers also drain water to control minerals. Minerals in must equal minerals out, so blowdown + drift = evaporation ÷ (cycles of concentration − 1) . The model samples 3 to 6 cycles, from the studies of data center cooling . FEMP calls two to four typical and six or more possible, a lower typical range, and no figure for large campuses is published [A]. At the middle of each range, 2 to 4 cycles would take about 17% more water than 3 to 6 (1.5 times the evaporation against 1.29), all of it as blowdown.
  5. Lost to evaporation and wastewater. Every gallon taken is either lost to evaporation (cooling, drift, leaks, humidifiers) or becomes wastewater, to the sewer or a stream (blowdown and nearly all sanitary use). Wastewater also carries the condensate from outside air, which was never taken from a water system. One rounding rule keeps them adding up: water taken to three significant figures, wastewater to the same place, each at the model's median, and water lost what is left, including the condensate. So the middle figure for water lost can sit a few percent above the model's own median for it (about 3% for cooling towers), since medians do not add. The ranges are the model's own. Numbers are shown to three significant figures (26,400; 6,180; 1.94 million), the same on every page and in the review, so that a difference the model resolves between two settings is not rounded away: cooling designs differ in electricity and power plant water by 1 to 3%. Three figures do not make the middle estimate that precise; the ranges say how sure it is. The rounded figures may not add up exactly. Multiples are shown to one decimal below 10 (7.4 times) and two significant figures above.
  6. Water that is not for cooling. Every design also takes some water that is not for cooling, in three parts (model 1.3). At 300 MW, staff water and maintenance together are about 7,200 gallons a day (4,400 to 10,000 across assumptions), about 900 of it lost. Staff water: restrooms, kitchens and cleaning for the people on site, which Microsoft says is all its zero-water design keeps water for . It follows the number of people, not the megawatts: people on site = 20 to 60 plus 0.1 to 0.5 per MW of computing capacity, times 10 to 30 gallons per person a day, so about 130 people and 2,300 gallons a day at 300 MW (middle of the runs). Gallons per person come from EPA's onsite wastewater manual, about 9 a calendar day for office and industrial workers , Michigan's septic design criteria, 35 per factory worker per shift , and one applicant's about 30 . People per MW follow announced campuses . Virginia's auditors put a typical building at about 50 full-time workers once open, about half of them contractors , and Michigan's sales tax exemption needs at least 30 new jobs . About 10% of staff water is lost (drinking, cleaning that dries; sampled 5 to 15%) and the rest goes down the drain . Maintenance and cleaning: washing equipment and floors, janitorial use, fire-system tests and loop flushing, up to 2,000 gallons a day for the campus plus 2 to 20 per MW, about 4,500 at 300 MW; 3 to 15% of it lost . No site publishes metered figures, so the range is bracketed by what applicants have projected [estimate]: Hermantown, Minnesota's loop maintenance at the low end, Crusoe's 200 MW building at the high end, checked against Saline Township and Microsoft's letter to Tyrone, Georgia. This is the largest uncertainty in this water. Loop top-up: a closed loop is filled once and loses a little to small leaks, typically under 5% of its volume a year ; the page samples 1 to 5% of a loop holding 2,000 to 12,000 gallons per MW of computing [estimate, from applicants' fills], all of it counted as lost. That is tens to a few hundred gallons a day. Outside air: the designs here cool with liquid loops, chillers or towers and recirculate the air inside the data halls, so outside air comes in only to pressurize and ventilate (model 1.5). The flow is sampled from 100 to 1,500 cfm per MW of computing capacity, an estimate: ASHRAE 62.1's 0.06 cfm per square foot for computer rooms at about 5,000 square feet per MW gives 300, and no published flow for large campuses was found. Above an indoor dew point of 15 °C a coil condenses the extra moisture; that condensate goes with the wastewater. It is clean water and would not go to a drainfield, so with a septic system the flow and Michigan's septic rules are worked out without it, and it is assumed to go to a site drain or stormwater [A]. Below −9 °C, humidifiers may add moisture, using water that is lost; how many campuses do this is not published, so the share is sampled from none to all . A design that cools with outside air directly would use far more air and is not modeled. Landscape watering is not counted, since it depends on the site and climate; ask how the site will be landscaped. Before model 1.2, this was one "base use" of 0.001 to 0.008 gallons per kWh of computing, 10 to 50% of it lost, which grew with the megawatts and counted humidification; at 300 MW it was about 26,000 gallons a day, four to seven times what Michigan applicants have projected (see the checks below).
  7. Cooling designs differ in when they evaporate: dry systems not at all; dry coolers with adiabatic pre-cooling evaporate water into the air ahead of the coil above a switch point. The switch point follows the loop: the dry-bulb where the dry coil can no longer supply the loop's water, give or take 2 K for operators who go wet early or trim with chillers a while longer. It is an operator's setting, within the settings makers publish [A] . The evaporation is calculated from how far the air is above its wet-bulb temperature, pad effectiveness of 70 to 80% , a 9 to 13 K air temperature rise from makers' selection sheets , and fans slowing in wet mode, with bleed of 0 to 50% of evaporation by pad type ; hybrids in warm weather, from the same switch point up to fully evaporative at each location's own 0.4% design dry-bulb, give or take 1.5 K [A]; cooling towers all year. These follow the system types in the national studies . The model runs the pads at full effectiveness above the switch temperature. A controller that wet the pads only enough to hold the air at the switch temperature would evaporate less: on central parameters at model 1.6, 12 to 41% less on average (West Michigan 41, Columbus 33, Ashburn 26, Austin 13, Houston 12) and 2 to 8% less on the peak day. Actual controls are not published, so the estimate is the higher of the two [A].
  8. Uncertainty. Real designs and operations vary, so every estimate is run 400 times across the parameter ranges below, on a Latin hypercube with linked parameters grouped. The calculator shows the middle result in bold and the middle 80% of runs as the range across assumptions, which is not a probability that the real value falls inside. Hybrid and assist results are noisy at 400 draws: on average days the median is good to about 10%, and the low end to about 42% in cool climates, where it is about 0.01 million gallons a day and should read as near zero. Cooling towers and PUE are good to 1 to 3%. Hybrid runs low against the figures operators have disclosed: see the checks below.

Mass and energy balances

Hourly energy balance per kW of IT load

INTHROUGH THE CAMPUSOUTOutside airIts heat and moisture: adds heatwhen hot or humid, takes someaway when cool or dryElectricityComputers (IT load)Power losses and lightingAir handler fansChillersPumpsHeat rejection fansHeat in the water or coilAn economizer carries whatthe weather allows; chillerscarry the rest and add theirown power. Air handler fansand pumps end up here too.A coil colder than the indoordew point removes moisturefrom outside air.Evaporationwet share × evaporative ratioWarm air from a towerwet share × (1 − ratio)Warm air from a dry cooler1 − wet shareWarm air from the fansstraight to the exhaustElectricity + heat from outside air = evaporation + warm air

Hourly water balance per kWh of IT load

INTHROUGH THE CAMPUSOUTWater takenFrom a water system, wellsor a lakeMoisture in outside airWhat the coil condensesTower or padsEvaporation, drift, blowdownLoop top-ups (small leaks)Humidifiers, in very dry airStaff and maintenanceRestrooms, kitchens, cleaningDehumidifying coil, in humid airMakes condensateEvaporated or lostEvaporationDriftLeaks from the loopHumidifier vaporA small part of staff waterWastewaterBlowdownCondensateMost staff and maintenancewaterTo a sewer, a septic systemor a stream, by the siteWater taken + condensate = water evaporated or lost + wastewater
Diagrams, not to scale. They describe the air- and water-cooled designs. Which paths carry anything depends on the design and the hour: closed loop has no tower or pads, and assist evaporates at pads ahead of a dry cooler. These balances hold in every hour of every run. Ranges are percentiles, and the ends of a range need not add up, but the middle estimates do.

The equations

  • Energy: facility power + outside air heat = heat through the water or coil + heat rejection fans
  • Heat through the water or coil: H = q + air handler fans + outside air heat + chillers + pumps, with q = 1/UPS + 1/(1 − distribution loss) − 1 + lighting per kW of IT
  • Chillers: load × (1 − economizer share) × (w / COP water-cooled + (1 − w) / COP air-cooled)
  • Tower fans: design fan power × (air needed / design air)³, from 10% of design air to all of it, where air needed goes with the tower's water over the enthalpy the air can pick up. Design is the 78 °F rating wet-bulb [A]. Dry cooler fans follow the same law.
  • Outside air heat: air flow × (enthalpy outside − enthalpy indoors). A dehumidifying coil carries the latent part.
  • Evaporation: H × w × evaporative ratio / latent heat. Assist evaporates at pads instead, from the air's own energy balance: H × depression / (switch point + air rise − air temperature + depression) / latent heat, where depression is pad effectiveness × (air temperature − wet-bulb).
  • Drift: H × w / (8.34 × range) × drift share
  • Blowdown: evaporation / (cycles − 1) − drift, from the dissolved solids balance: makeup × solids = (blowdown + drift) × cycles × solids
  • Water: withdrawn + condensate = consumed + returned. The middle estimate takes withdrawn and returned at their medians, and consumed is the remainder.
  • Lake-source: flow × density × specific heat × rise = heat = electricity, since the lake water is colder than the loops and needs no chillers or heat rejection fans [A]. Withdrawn equals returned at the pipe. The added heat then drives evaporation from the lake surface, so that balance is the lake's.
  • Power plants, off site: generation = campus electricity / (1 − line loss). Plant water is generation × water per MWh generated, reported separately and never added to the campus's own water.

Terms

IT load, IT capacityThe power the computers draw, and the most they can draw. Utilization is load over capacity.
Facility power, PUEAll the electricity the campus uses. Power usage effectiveness (PUE) is facility power over IT load.
Sensible and latent heatSensible heat changes the temperature of air or water. Latent heat evaporates or condenses water without changing its temperature, about 1,050 BTU per pound.
EnthalpyThe heat air carries, sensible and latent together.
EconomizerCooling without running a chiller, when outside conditions are cold enough.
Chiller, COPA machine that moves heat from cool water to warmer surroundings using electricity. Its coefficient of performance (COP) is heat moved per unit of electricity.
Wet share (w)The share of the heat going through evaporation: 1 for towers, 0 for closed loop and assist coils, and rising with air temperature for hybrid.
Evaporative ratioThe share of a tower's heat that leaves by evaporation, the rest warming the air. It rises with air temperature (Rutberg et al. 2011, as in USGS SIR 2013-5188).
RangeHow much a tower cools its water, °F.
DriftDroplets carried out of a tower in the air.
BlowdownWater drained from a tower to keep dissolved minerals from building up. Pads drain a similar bleed.
Cycles of concentrationHow many times more concentrated the tower's water is than the water coming in.
Loop top-upWater replacing small leaks from a closed loop.
Outside airAir brought in to pressurize and ventilate the building. It is a small flow, 100–1,500 cfm per MW of IT capacity [A], not used for cooling.
Dew point, condensateAir cooled to its dew point starts to condense. Above the 15 °C indoor limit, a coil removes the extra moisture as condensate, water that comes from the air and not from the water system.
HumidifierAdds moisture when the air's dew point is below −9 °C. How many campuses do this is not published, so the share is sampled from none to all [A].
Withdrawn, consumed, returnedThe model's names for water taken; water evaporated or lost as droplets and leaks; and wastewater, sent to a sewer, septic system or stream.
Line lossElectricity lost between power plants and the campus, about 5% (EIA, U.S. average 2018–2022). The national figure is used in every state, and a campus on the transmission system may lose less [A].

Parameters

The base overhead against operators' figures. Every cooling design carries the same base overhead in its electricity: losses in the uninterruptible power supplies, with efficiency sampled from 0.90 to 0.99, the range Lei and Masanet use for large sites and LBNL's 2024 report uses for hyperscale sites ; up to 2% lost in distribution; lighting; and the air handler fans. With it, a campus on cooling towers runs at a yearly PUE of about 1.13 to 1.16 in the model, from Grand Rapids to Dallas (our runs, model 1.17). That is above what the largest operators report for their evaporative fleets: Google about 1.09 across its fleet , Meta 1.08 (2025 Environmental Data Index) and AWS 1.12 to 1.15 by region (AWS fact sheets). It is below Uptime Institute's 2025 survey averages, 1.44 for sites of 20 MW or more and 1.48 for sites built since about 2020 (Global Data Center Survey 2025, p. 7), and Crusoe's design range of 1.2 to 1.4 for its campus at Abilene, Texas (Crusoe). We keep the range as a planning estimate for a campus whose operator and equipment are not yet known [A]. It moves every design's PUE together, so it does not change the difference between designs: in Loudoun County, Virginia, UPS efficiency at 0.99 instead of its middle value lowers towers from 1.139 to 1.087 and dry cooling from 1.188 to 1.134, and dry stays 4.3% above towers (our calculation, model 1.17, every other parameter at its middle value).

Results by region (a 100 MW campus)

Middle result with the range across assumptions (10th–90th percentile), for 100 MW of computing capacity including staff water at that size. Staff water grows more slowly than the computers, so a 300 MW campus takes less than three times these amounts with closed loop. "Water per kWh" is per kilowatt-hour of computing energy, for the model's cooling and loop water without staff water: evaporated, and taken (the basis national studies report).

Checks against reported use

Most operators do not publish a site's size, so few site-by-site checks are possible. We are not aware of a published study that checks a site-level data center water model against metered use at named sites; we show what we can, with its limits.

Water at power plants

Electricity and power plant water

Lake-source cooling and wastewater

Runoff and water quality

A screening estimate of what the campus does to runoff and to the streams it reaches, before and after. The same calculation runs in Water Ledger's Python models (waterledger_models.runoff), and every parameter comes from one file, so the page and any report agree.

Before and after

Starting assumptions

Each setting starts from what is known, and a short note says which: Known (published for a proposal), Your place (from public data for the place) or Assumed. Every setting can be changed.

Local facts

Every Michigan city and township (1,541 places with land area in the Census list) has a profile built from public data only:

Limitations

About the data

Water Ledger is built and kept current by Northline Hydrology. Everything in Water Ledger comes from public records, published sources and our own models. No client work or data appears here. It does not rate projects as good or bad; it shows what they could mean for water so people can decide with numbers instead of guesses.

Sources

    What has changed in the numbers, and when: changelog. See something wrong? Suggest a correction.